Description
Nova’s Jupiter-Series UPS Systems are high-reliability power sources specifically designed for demanding commercial and heavy industrial applications which require UL1778 Certification. These models utilize True On-Line technology and the most durable components, offering maximum field-proven reliability for severe environment and high reliability applications. Please note: Any Jupiter UPS shown herein can be used with larger batteries to obtain higher run times. 75AH, 88AH and 100AH batteries are also available – consult factory for run times.
Specifications
Specifications for the Nova Jupiter-Series UL1778 Certified Three-Phase UPS Series
PHASE |
3-Phase Input/ 3-Phase Output |
KVA |
10 |
15 |
20 |
30 |
40 |
50 |
60 |
Input Rectifier |
|
Input Voltage (VAC) |
120/208 VAC |
Input Range |
+/- 20% (>+20% is available upon request) |
Input Frequency |
50/ 60 + 5Hz |
Power Walk In |
0% – 100% :20 sec |
Voltage Regulation |
1% |
Efficiency |
98% |
Rectification Type |
6 Pulse Standard, 12 Pulse Optional |
Battery |
|
Battery Type |
Maintenance free lead-acid batteries/ 12V (348 VDC Nominal) |
Maximum Charge Current(Adc Selectable)LO,MED,HI |
4 |
8 |
8 |
12 |
16 |
25 |
26 |
Battery Start |
Yes, UPS can be started without AC source. |
Inverter |
|
Output Voltage (VAC) |
120/208 |
Wave Form |
Sinewave |
Output Power Factor |
0.8 |
Frequency Lock Range |
50 / 60 Hz +/- 3 Hz |
Output Frequency (Free Running) |
50 / 60 Hz +0.1Hz (crystal controlled) |
Output Frequency (free running) |
0.7 lead to lag |
Phase Shift Under 100% Unbalanced Load |
<0.5% |
THD (Linear Load) |
< 2% |
Overload |
<110% |
Continuous |
>110-125% |
Up to 15 minutes |
>125-150% |
Up to 5 minutes |
>150-170% |
Up to 30 seconds |
>170-200% |
Up to 15 seconds |
Efficiency (100% Load) |
93% |
93% |
93% |
93% |
93.5% |
93.5% |
94% |
STATIC SWITCH |
|
Voltage Range |
Same as Main Rectifier Input.(Different voltages are available upon request) |
Mains <-> Inverter |
0 ms (True Online) |
Overload |
As per inverter rating plus >200% to 300% = 1 second |
OVERALL CHARACTERISTICS |
|
Overall Efficiency |
91% |
91% |
91% |
91% |
91.5% |
92% |
92% |
Maximum Heat Dissipation (kw) |
0.7 |
1.1 |
1.4 |
1.9 |
2.6 |
3 |
3.5 |
BTU/h @ Full Load |
2.4K |
3.6K |
4.8K |
6.5K |
8.9K |
10.3K |
12K |
Audible Noise |
<65 dBA (at 1m) |
Temperature |
0-40ºC (32-104ºF)(Other ranges available) |
Humidity |
0%-95% (Non-condensing) |
Altitude |
<1500 m Above Sea Level |
MTTR |
Less Than 30 minutes |
EN50091-1, -2 |
Yes |
Short Circuit Protection |
Yes |
MTBF |
As per Field Experience >100,000 Hours for loss of AC Output |
Lightning / EMC Filter |
MOV / Input & Output ( FCC Class A) |
Galvanic Isolation |
Input and Output True Galvanic Isolation |
LED, LCD, Audible Alarm |
Yes |
Remote Control and Communication Interface Choices |
Dry Contact, RS-232, RS-485 (Optional,) UPScan Monitoring 1~99 Units Simultaneously (Optional,) Netagent (Optional,) MODBUS (Optional) |
MONITORING FEATURES
- The unit includes an RS232 communication option called UPSCOM which can monitor the output parameters and any abnormal conditions that have occurred in real time.
FRONT PANEL LCD DISPLAY AND LED INDICATORS
- This will report all UPS parameters including input and output voltages, currents, frequency, battery voltage, battery current, and many other functions.
LCD DISPLAY
- Real time status, data, and historical events are displayed via the LCD display. The UPS parameters, real-time clock, inverter, and buzzer can also be set through this LCD, which is backlit by LEDs for visual clarity.
STATUS LEDs
LEDs representing all important operational information provide feedback to the user. LED descriptions are as follows:
- UPS ON – UPS is running normally.
- UPS SS – UPS static switch is on while the reserve static switch is opened (off).
- SHORT CIRCUIT – UPS output is in short circuit state.
- FUSE / OVERTEMP SD – UPS has shut down due to either fuse open or over temperature.
- UPS FAIL SHUTDOWN – UPS has shut down due to low inverter AC output voltage.
- BYPASS ON SHUTDOWN –UPS shut down due to closed bypass breaker. UPS shut down due closed bypass breaker (while inverter running).
- HIGH DC SHUTDOWN – UPS shut down due to high DC bus.
- OVERLOAD SHUTDOWN – UPS shutdown due to overload of the inverter for a period greater than the inverter can accept. The UPS will start after 7 seconds.
70% LOAD – load connected to the output is over 70% of the Inverter rating.
110% LOAD – load connected to the output is over 110% oh the Inverter rating.
125% LOAD – load connected to the output is over 125% of the Inverter rating.
150% LOAD – load connected to the output is over 150% of the Inverter rating.
- RESERVE AC FAIL – reserve AC magnitude is out of range.
- RESERVE FREQ FAIL – reserve frequency is out of range.
- BATTERY LOW – DC bus (or battery) is lower than specified range, low battery shutdown will occur soon.
- BATTERY LOW SHUTDOWN – inverter shutdown due to DC bus (or battery) lower than the acceptable DC voltage of the inverter.
- HIGH DC – DC voltage over the acceptable DC voltage of the inverter.
- EMERGENCY STOP – Inverter shut down activated by emergency stop switch.
- DATA LINE – Blink when data is transmitted to or received from the communication port
WARNING LEDs
When abnormal condition occurs, these LEDs will light to warn the user of the cause of the fault condition. These LEDs are:
- RESERVE FAIL – Reserve AC input is abnormal either due to AC magnitude out of range or frequency out of range.
- FUSE/TEMP – Either inverter fuse is open or over temperature has occurred.
- OVERLOAD – Output is overloaded by over 110%, 125% or 150%
- HIGH DC – This LED will light when DC input approaches high-line limit.
- BAT LOW – This LED will light when the DC voltage is low.
- BAT LOW STOP – This LED will light when the DC voltage is lower than specified range.
- FAULT – The inverter is off due to abnormal conditions such as overload, short circuit, high DC, fuse over temperature, bypass breaker on emergency stop.
AUDIBLE ALARM
The audible alarm will beep under either one of the following conditions:
- INVERTER IS OVERLOADED –
> 110% beep once every 3 seconds
> 125% beep once every second
> 150% beep twice every second
- INVERTER IS SHORT CIRCUITED – Beeps continuously
- FUSE OPEN– Beeps continuously
- HEAT SINK OVER TEMPERATURE – Beeps continuously
- HIGH DC SHUTDOWN – Beeps continuously
- BYPASS ON STOP – Beeps continuously
- EMERGENCY ON STOP – Beeps continuously
The buzzer will also beep once every time the inverter is switched on or off to acknowledge to the user that his key entry is valid and accepted.temperature, bypass breaker on emergency stop.